PACKETFLUX-STANDBYPOWER: View SNMP OID List / Download MIB

VENDOR: PACKETFLUX TECHNOLOGIES


 Home MIB: PACKETFLUX-STANDBYPOWER
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 standbypower 1.3.6.1.4.1.32050.2.2
MIB for the PacketFlux Standby Power Controller
     powercontrollerstate 1.3.6.1.4.1.32050.2.2.1 integer read-only
The status of the standby power controller. Enumeration: 'startingstandby': 2, 'transferringtoprimary': 5, 'onprimarypower': 1, 'transferringtostandby': 3, 'onstandbypower': 4.
     transferswitchstate 1.3.6.1.4.1.32050.2.2.2 integer read-only
The current state in the transfer sequence. Enumeration: 'transfertoprimary2': 7, 'transfertoprimary3': 8, 'transfertoprimary1': 6, 'transfertostandby1': 2, 'transfertostandby3': 4, 'transfertostandby2': 3, 'primary': 1, 'standby': 5.
     standbypowerstate 1.3.6.1.4.1.32050.2.2.3 integer read-only
The current state in the standby power sequence. Enumeration: 'warmup3': 14, 'warmup2': 13, 'warmup1': 12, 'prepare3': 4, 'prepare2': 3, 'prepare1': 2, 'cooldown1': 17, 'cooldown2': 18, 'cooldown3': 19, 'postshutdown1': 24, 'postshutdown3': 26, 'postshutdown2': 25, 'checkrun': 8, 'shutdown3': 22, 'shutdown2': 21, 'running': 16, 'startup1': 5, 'startup3': 7, 'startup2': 6, 'reprepare2': 10, 'reprepare3': 11, 'shutdown1': 20, 'reprepare1': 9, 'verifystopped': 23, 'stopped': 1, 'verifyrun': 15.
     ac1voltage 1.3.6.1.4.1.32050.2.2.4 gauge32 read-only
The voltage of the AC input AC1 in 1/10ths of a volt.
     ac1frequency 1.3.6.1.4.1.32050.2.2.5 gauge32 read-only
The frequency of the AC input AC1 in 1/100ths of a Hertz.
     ac2voltage 1.3.6.1.4.1.32050.2.2.6 gauge32 read-only
The voltage of the AC input AC2 in 1/10ths of a volt.
     ac2frequency 1.3.6.1.4.1.32050.2.2.7 gauge32 read-only
The frequency of the AC input AC2 in 1/100ths of a Hertz.
     mtr1voltage 1.3.6.1.4.1.32050.2.2.8 gauge32 read-only
The voltage of the DC input Mtr1 in 1/10ths of a volt.
     mtr2voltage 1.3.6.1.4.1.32050.2.2.9 gauge32 read-only
The voltage of the DC input Mtr2 in 1/10ths of a volt.
     pwr1voltage 1.3.6.1.4.1.32050.2.2.10 gauge32 read-only
The voltage of the DC input Pwr3 in 1/10ths of a volt.
     pwr2voltage 1.3.6.1.4.1.32050.2.2.11 gauge32 read-only
The voltage of the DC input Pwr2 in 1/10ths of a volt.
     shuntvoltage 1.3.6.1.4.1.32050.2.2.12 integer32 read-only
The voltage of the DC input Shunt in 1/10ths of a millivolt. Can be negative.
     temperature 1.3.6.1.4.1.32050.2.2.13 gauge32 read-only
The temperature of the onboard temperature sensor in 1/10ths of a degree centigrade.
     recentunsuccessfulstarts 1.3.6.1.4.1.32050.2.2.14 integer32 read-write
The number of times the standby power source was not successfully started. This counter resets upon a successful start. It can also be reset via the web interface or by writing 0 to this object.
     totalunsuccessfulstarts 1.3.6.1.4.1.32050.2.2.15 integer32 read-write
The number of times the standby power source was not successfully started. This counter DOES NOT reset upon a successful start. It can be reset via the web interface or by writing 0 to this object.
     recentstalls 1.3.6.1.4.1.32050.2.2.16 integer32 read-write
The number of times the standby power source has stalled. This counter resets upon a clean shutdown. It can also be reset via the web interface or by writing 0 to this object.
     totalstalls 1.3.6.1.4.1.32050.2.2.17 integer32 read-write
The number of times the standby power source has stalled. This counter DOES NOT reset upon a clean shutdown. It can be reset via the web interface or by writing 0 to this object.
     numberofstarts 1.3.6.1.4.1.32050.2.2.18 integer32 read-write
The number of times the secondary power source has started. This counter increments when the standby sequence reaches the running state. This counter can be reset via the web interface or by writing 0 to this object.
     numberoftransfers 1.3.6.1.4.1.32050.2.2.19 integer32 read-write
The number of times the power has transfered from primary to standby, or back. A complete transfer cycle from primary to standby and back to primary will increment this counter twice. This counter can be reset via the web interface or by writing 0 to this object.
     currenttimeonprimary 1.3.6.1.4.1.32050.2.2.20 timeticks read-write
The amount of time the transfer switch has been in the primary state (position) since the most recent transfer to that state. This timer resets to zero when the transfer switch leaves the primary state (position). This timer can be reset via the web interface or by writing 0 to this object.
     totaltimeonprimary 1.3.6.1.4.1.32050.2.2.21 timeticks read-write
The amount of time the transfer switch has been in the primary state (position) since power on or the last reset of this counter. This timer does not automatically reset. This timer can be reset via the web interface or by writing 0 to this object.
     currenttimeonstandby 1.3.6.1.4.1.32050.2.2.22 timeticks read-write
The amount of time the transfer switch has been in the standby state (position) since the most recent transfer to that state. This timer resets to zero when the transfer switch leaves the primary state (position). This timer can be reset via the web interface or by writing 0 to this object.
     totaltimeonstandby 1.3.6.1.4.1.32050.2.2.23 timeticks read-write
The amount of time the transfer switch has been in the standby state (position) since power on or the last reset of this counter. This timer does not automatically reset. This timer can be reset via the web interface or by writing 0 to this object.
     currentstandbyruntime 1.3.6.1.4.1.32050.2.2.24 timeticks read-write
The amount of time the standby power source has been running during it's current run. This timer resets to zero when the standby power source shuts down. This timer can be reset via the web interface or by writing 0 to this object.
     totalstandbyruntime 1.3.6.1.4.1.32050.2.2.25 timeticks read-write
The amount of time the standby power source has been running since power on or the last reset of this counter. This timer does not automatically reset. This timer can be reset via the web interface or by writing 0 to this object.
     laststandbyrun 1.3.6.1.4.1.32050.2.2.26 timeticks read-write
The amount of time since the standby power source ran last. This timer resets upon start of the standby power source and starts timing upon shutdown of the standby power source. This timer can be reset via the web interface or by writing 0 to this object.
     laststandbygracefulstop 1.3.6.1.4.1.32050.2.2.27 timeticks read-write
The amount of time since standby power source was gracefully shutdown. This timer resets and starts timing upon graceful shutdown of the standby power source. This timer can be reset via the web interface or by writing 0 to this object.
     laststandbyunsuccessfulstart 1.3.6.1.4.1.32050.2.2.28 timeticks read-write
The amount of time since the last failed start of the standby power source . This timer resets and starts timing upon a unsuccessful start of the power source. This timer can be reset via the web interface or by writing 0 to this object.
     laststandbyfailure 1.3.6.1.4.1.32050.2.2.29 timeticks read-write
The amount of time since the stall or failure while running of the standby power source . This timer resets and starts timing upon a stall/failure of the power source. This timer can be reset via the web interface or by writing 0 to this object.
     switch1closed 1.3.6.1.4.1.32050.2.2.30 truthvalue read-only
True(1) if the Switch 1 input is closed (shorted/on). False(2) if it is open.
     switch2closed 1.3.6.1.4.1.32050.2.2.31 truthvalue read-only
True(1) if the Switch 2 input is closed (shorted/on). False(2) if it is open.
     switch3closed 1.3.6.1.4.1.32050.2.2.32 truthvalue read-only
True(1) if the Switch 3 input is closed (shorted/on). False(2) if it is open.
     switch4closed 1.3.6.1.4.1.32050.2.2.33 truthvalue read-only
True(1) if the Switch 4 input is closed (shorted/on). False(2) if it is open.
     switch5closed 1.3.6.1.4.1.32050.2.2.34 truthvalue read-only
True(1) if the Switch 5 input is closed (shorted/on). False(2) if it is open.
     enabled 1.3.6.1.4.1.32050.2.2.35 truthvalue read-only
True(1) if the enable input is closed (shorted/on). False(2) if it is open.
     relay1on 1.3.6.1.4.1.32050.2.2.36 truthvalue read-only
True(1) if the Relay 1 ouput is on (C and NO connected). False(2) if it is off (C and NC connected).
     relay2on 1.3.6.1.4.1.32050.2.2.37 truthvalue read-only
True(1) if the Relay 2 ouput is on (C and NO connected). False(2) if it is off (C and NC connected).
     relay3on 1.3.6.1.4.1.32050.2.2.38 truthvalue read-only
True(1) if the Relay 3 ouput is on (C and NO connected). False(2) if it is off (C and NC connected).
     relay4on 1.3.6.1.4.1.32050.2.2.39 truthvalue read-only
True(1) if the Relay 4 ouput is on (C and NO connected). False(2) if it is off (C and NC connected).
     relay5on 1.3.6.1.4.1.32050.2.2.40 truthvalue read-only
True(1) if the Relay 5 output is on (C and NO connected). False(2) if it is off (C and NC connected).
     relay6on 1.3.6.1.4.1.32050.2.2.41 truthvalue read-only
True(1) if the Relay 6 output is on (C and NO connected). False(2) if it is off (C and NC connected).
     relay7on 1.3.6.1.4.1.32050.2.2.42 truthvalue read-only
True(1) if the Relay 7 output is on (C and NO connected). False(2) if it is off (C and NC connected).
     ruleswitchstandby 1.3.6.1.4.1.32050.2.2.43 truthvalue read-only
True(1) if the switch to standby rule is true. False(2) if it is not.
     rulereturnprimary 1.3.6.1.4.1.32050.2.2.44 truthvalue read-only
True(1) if the return to primary rule is true. False(2) if it is not.
     rulestandbygood 1.3.6.1.4.1.32050.2.2.45 truthvalue read-only
True(1) if the standby power good rule is true. False(2) if it is not.
     rulestopstandby 1.3.6.1.4.1.32050.2.2.46 truthvalue read-only
True(1) if the stop standby and consider it failed rule is true. False(2) if it is not.
     ruleexercisestandby 1.3.6.1.4.1.32050.2.2.47 truthvalue read-only
True(1) if the exercise standby without transfer rule is true. False(2) if it is not.
     webcontrol1 1.3.6.1.4.1.32050.2.2.48 truthvalue read-write
True(1) if the webcontrol 1 virtual toggle switch is in the on position. False(2) if it is not. This value can be written to affect the position of the toggle switch.
     webcontrol2 1.3.6.1.4.1.32050.2.2.49 truthvalue read-write
True(1) if the webcontrol 2 virtual toggle switch is in the on position. False(2) if it is not. This value can be written to affect the position of the toggle switch.
     webcontrol3 1.3.6.1.4.1.32050.2.2.50 truthvalue read-write
True(1) if the webcontrol 3 virtual toggle switch is in the on position. False(2) if it is not. This value can be written to affect the position of the toggle switch.
     webcontrol4 1.3.6.1.4.1.32050.2.2.51 truthvalue read-write
True(1) if the webcontrol 4 virtual toggle switch is in the on position. False(2) if it is not. This value can be written to affect the position of the toggle switch.
     webcontrol5 1.3.6.1.4.1.32050.2.2.52 truthvalue read-write
True(1) if the webcontrol 5 virtual toggle switch is in the on position. False(2) if it is not. This value can be written to affect the position of the toggle switch.
     webcontrol6 1.3.6.1.4.1.32050.2.2.53 truthvalue read-write
True(1) if the webcontrol 6 virtual toggle switch is in the on position. False(2) if it is not. This value can be written to affect the position of the toggle switch.
     webcontrol7 1.3.6.1.4.1.32050.2.2.54 truthvalue read-write
True(1) if the webcontrol 7 virtual toggle switch is in the on position. False(2) if it is not. This value can be written to affect the position of the toggle switch.
     webcontrol8 1.3.6.1.4.1.32050.2.2.55 truthvalue read-write
True(1) if the webcontrol 8 virtual toggle switch is in the on position. False(2) if it is not. This value can be written to affect the position of the toggle switch.
     standbypowerConformance 1.3.6.1.4.1.32050.2.2.256
             standbypowerGroups 1.3.6.1.4.1.32050.2.2.256.1
                 packetfluxStandbypowerAllObjects 1.3.6.1.4.1.32050.2.2.256.1.1
This automatically created object group contains all those objects that do not belong to any other OBJECT-GROUP