LIEBERT-SERIES-300-UPS-MIB: View SNMP OID List / Download MIB

VENDOR: VERTIV


 Home MIB: LIEBERT-SERIES-300-UPS-MIB
Download as:   

Download standard MIB format if you are planning to load a MIB file into some system (OS, Zabbix, PRTG ...) or view it with a MIB browser. CSV is more suitable for analyzing and viewing OID' and other MIB objects in excel. JSON and YAML formats are usually used in programing even though some systems can use MIB in YAML format (like Logstash).
Keep in mind that standard MIB files can be successfully loaded by systems and programs only if all the required MIB's from the "Imports" section are already loaded.
The tree-like SNMP object navigator requires no explanations because it is very simple to use. And if you stumbled on this MIB from Google note that you can always go back to the home page if you need to perform another MIB or OID lookup.


Object Name OID Type Access Info
 emerson 1.3.6.1.4.1.476
         liebertCorp 1.3.6.1.4.1.476.1
             liebertUps 1.3.6.1.4.1.476.1.1
                 luExtensions 1.3.6.1.4.1.476.1.1.1
                     luCore 1.3.6.1.4.1.476.1.1.1.1
                         lcUpsIdent 1.3.6.1.4.1.476.1.1.1.1.1
                             lcUpsIdentManufacturer 1.3.6.1.4.1.476.1.1.1.1.1.1 displaystring read-only
The UPS manufacturer.
                             lcUpsIdentModel 1.3.6.1.4.1.476.1.1.1.1.1.2 displaystring read-write
The UPS Model designation.
                             lcUpsIdentSoftwareVersion 1.3.6.1.4.1.476.1.1.1.1.1.3 displaystring read-only
The UPS SNMP Agent software version.
                             lcUpsIdentSpecific 1.3.6.1.4.1.476.1.1.1.1.1.4 object identifier read-only
A reference to MIB definitions specific to the particular UPS being managed. This object is used to locate the product-specific MIB for this device. If this information is not present, its value should be the OBJECT IDENTIFIER { 0 0 }, which is a syntactically valid object identifier, and any conformant implementation of ASN.1 and BER must be able to generate and recognize this value.
                         lcUpsBattery 1.3.6.1.4.1.476.1.1.1.1.2
                             lcUpsBatTimeRemaining 1.3.6.1.4.1.476.1.1.1.1.2.1 integer read-only
The estimated time to depletion of battery charge. (Unit of measure: Minute)
                             lcUpsBatTemperature 1.3.6.1.4.1.476.1.1.1.1.2.2 integer read-only
The battery temperature. (Unit of measure: Degree, Centigrade)
                             lcUpsBatVoltage 1.3.6.1.4.1.476.1.1.1.1.2.3 integer read-only
The current battery voltage. (Unit of measure: volt)
                             lcUpsBatCurrent 1.3.6.1.4.1.476.1.1.1.1.2.4 integer read-only
The current battery discharging/charging current. (Unit of measure: Amp)
                         lcUpsInput 1.3.6.1.4.1.476.1.1.1.1.3
                             lcUpsInputFrequency 1.3.6.1.4.1.476.1.1.1.1.3.1 integer read-only
The current input frequency. (Unit of measure: Hertz)
                             lcUpsInputBrownOuts 1.3.6.1.4.1.476.1.1.1.1.3.2 counter read-only
The number of brown-out conditions the UPS has experienced.
                             lcUpsInputBlackOuts 1.3.6.1.4.1.476.1.1.1.1.3.3 counter read-only
The number of black-out conditions the UPS has experienced.
                             lcUpsInputTransients 1.3.6.1.4.1.476.1.1.1.1.3.4 counter read-only
The number of transient (surge and spike) conditions the UPS has experienced.
                             lcUpsInputNumLines 1.3.6.1.4.1.476.1.1.1.1.3.5 integer read-only
The number of input lines utilized in this device. This entry indicates the number of rows in the input table.
                             lcUpsInputTable 1.3.6.1.4.1.476.1.1.1.1.3.6 no-access
                                 lcUpsInputEntry 1.3.6.1.4.1.476.1.1.1.1.3.6.1 no-access
                                     lcUpsInputLine 1.3.6.1.4.1.476.1.1.1.1.3.6.1.1 integer read-only
The input Line.
                                     lcUpsInputVoltage 1.3.6.1.4.1.476.1.1.1.1.3.6.1.2 integer read-only
The input voltage. (Unit of measure: Volt)
                                     lcUpsInputCurrent 1.3.6.1.4.1.476.1.1.1.1.3.6.1.3 integer read-only
The input current. (Unit of measure: Amp)
                                     lcUpsInputVA 1.3.6.1.4.1.476.1.1.1.1.3.6.1.4 integer read-only
The input volt-amps.
                         lcUpsOutput 1.3.6.1.4.1.476.1.1.1.1.4
                             lcUpsOutputFrequency 1.3.6.1.4.1.476.1.1.1.1.4.1 integer read-only
The current output frequency. (Unit of measure: Hertz)
                             lcUpsOutputLoad 1.3.6.1.4.1.476.1.1.1.1.4.2 integer read-only
The current output load percentage.
                             lcUpsOutputNumLines 1.3.6.1.4.1.476.1.1.1.1.4.3 integer read-only
The number of output lines utilized in this device. This entry indicates the number of rows in the output table.
                             lcUpsOutputTable 1.3.6.1.4.1.476.1.1.1.1.4.4 no-access
                                 lcUpsOutputEntry 1.3.6.1.4.1.476.1.1.1.1.4.4.1 no-access
                                     lcUpsOutputLine 1.3.6.1.4.1.476.1.1.1.1.4.4.1.1 integer read-only
The output Line.
                                     lcUpsOutputVoltage 1.3.6.1.4.1.476.1.1.1.1.4.4.1.2 integer read-only
The output voltage. (Unit of measure: Volt)
                                     lcUpsOutputCurrent 1.3.6.1.4.1.476.1.1.1.1.4.4.1.3 integer read-only
The output current. (Unit of measure: Amp)
                                     lcUpsOutputVA 1.3.6.1.4.1.476.1.1.1.1.4.4.1.4 integer read-only
The output volt-amps.
                         lcUpsInverter 1.3.6.1.4.1.476.1.1.1.1.5
                             lcUpsInverterStatus 1.3.6.1.4.1.476.1.1.1.1.5.1 integer read-only
The state of the inverter. Unknown is returned if the state can not be determined. Enumeration: 'unknown': 1, 'off': 3, 'on': 2.
                             lcUpsInverterTemp 1.3.6.1.4.1.476.1.1.1.1.5.2 integer read-only
The temperature of the inverter. (Unit of measure: degree, Centigrade)
                         lcUpsAlarm 1.3.6.1.4.1.476.1.1.1.1.6
                             lcUpsAlarms 1.3.6.1.4.1.476.1.1.1.1.6.1 gauge read-only
The current number of alarm conditions.
                             lcUpsAlarmTable 1.3.6.1.4.1.476.1.1.1.1.6.2 no-access
                                 lcUpsAlarmEntry 1.3.6.1.4.1.476.1.1.1.1.6.2.1 no-access
                                     lcUpsAlarmId 1.3.6.1.4.1.476.1.1.1.1.6.2.1.1 integer read-only
A unique identifier for an alarm condition. This value must remain constant between agent initializations.
                                     lcUpsAlarmDescr 1.3.6.1.4.1.476.1.1.1.1.6.2.1.2 object identifier read-only
A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.
                                     lcUpsAlarmTime 1.3.6.1.4.1.476.1.1.1.1.6.2.1.3 timeticks read-only
The value of sysUpTime when the alarm condition occured.
                             lcUpsAlarmConditions 1.3.6.1.4.1.476.1.1.1.1.6.3
                                 lcUpsAlarmLowBatteryWarning 1.3.6.1.4.1.476.1.1.1.1.6.3.1
                                 lcUpsAlarmLowBatteryShutdown 1.3.6.1.4.1.476.1.1.1.1.6.3.2
                                 lcUpsAlarmUtilFailed 1.3.6.1.4.1.476.1.1.1.1.6.3.3
                                 lcUpsAlarmOverTempWarning 1.3.6.1.4.1.476.1.1.1.1.6.3.4
                                 lcUpsAlarmOutputOverloadWarning 1.3.6.1.4.1.476.1.1.1.1.6.3.6
                                 lcUpsAlarmInputOverVoltage 1.3.6.1.4.1.476.1.1.1.1.6.3.8
                                 lcUpsAlarmBatteryBad 1.3.6.1.4.1.476.1.1.1.1.6.3.9
                                 lcUpsAlarmOnBattery 1.3.6.1.4.1.476.1.1.1.1.6.3.10
                                 lcUpsAlarmUpsOff 1.3.6.1.4.1.476.1.1.1.1.6.3.12
                         lcUpsTest 1.3.6.1.4.1.476.1.1.1.1.7
                             lcUpsTestBattery 1.3.6.1.4.1.476.1.1.1.1.7.1 integer read-write
Setting this variable to 'start' will initiate the battery test. Setting this variable to 'abort' will stop the battery test if the test is in- progress, otherwise it has no effect. Setting this variable to 'unknown' has no effect. Reading this variable will always result in a return value of 'unknown'. If 'lcUpsTestBatteryStatus' is 'failed' the test may not be performed again and the status will remain in the failure state. Enumeration: 'unknown': 1, 'abort': 3, 'start': 2.
                             lcUpsTestBatteryStatus 1.3.6.1.4.1.476.1.1.1.1.7.2 integer read-only
The status of the battery test. Enumeration: 'unknown': 1, 'failed': 3, 'inhibited': 7, 'sysFailure': 5, 'passed': 2, 'inProgress': 4, 'notSupported': 6.
                             lcUpsTestDiag 1.3.6.1.4.1.476.1.1.1.1.7.3 integer read-write
Setting this variable to 'start' will initiate the diagnostics test. Setting this variable to 'abort' will stop the diagnostics test if the test is in-progress, otherwise it has no effect. Setting this variable to 'unknown' has no effect. Reading this variable will always result in a return value of 'unknown'. Enumeration: 'unknown': 1, 'abort': 3, 'start': 2.
                             lcUpsTestDiagStatus 1.3.6.1.4.1.476.1.1.1.1.7.4 integer read-only
The status of the diagnostics test. Enumeration: 'unknown': 1, 'failed': 3, 'inhibited': 7, 'sysFailure': 5, 'passed': 2, 'inProgress': 4, 'notSupported': 6.
                         lcUpsControl 1.3.6.1.4.1.476.1.1.1.1.8
                             lcUpsControlOutputOffDelay 1.3.6.1.4.1.476.1.1.1.1.8.1 integer read-write
Setting this object causes the agent to instruct the UPS to turn off the output after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsOutputOffTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value cancel.
                             lcUpsControlOutputOnDelay 1.3.6.1.4.1.476.1.1.1.1.8.2 integer read-write
Setting this object causes the agent to instruct the UPS to turn on the output after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsOutputOnTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value cancel.
                             lcUpsControlOutputOffTrapDelay 1.3.6.1.4.1.476.1.1.1.1.8.3 integer read-write
When 'lcUpsControlOutputOffDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOffWarningTrap will be produced and this object will be reset to 0.
                             lcUpsControlOutputOnTrapDelay 1.3.6.1.4.1.476.1.1.1.1.8.4 integer read-write
When 'lcUpsControlOutputOnDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOnWarningTrap will be produced and this object will be reset to 0.
                             lcUpsControlUnixShutdownDelay 1.3.6.1.4.1.476.1.1.1.1.8.5 integer read-write
Setting this object causes the agent to instruct the UPS to perform a UNIX Shutdown in the indicated number of seconds. The agent counts down the number of seconds until the event will take place. A Unix shutdown is only valid if the UPS is on Battery. During a UNIX Shutdown, the UPS will turn off the output even if the Utility comes back on line before the shutdown time arrives. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value 'cancel'.
                             lcUpsControlUnixShutdownTrapDelay 1.3.6.1.4.1.476.1.1.1.1.8.6 integer read-write
When 'lcUpsControlUnixShutdownDelay' reaches a value less than or equal to this object's value, an lcUpsUnixShutdownWarningTrap will be produced and this object will be reset to 0.
                             lcUpsControlCancelCommands 1.3.6.1.4.1.476.1.1.1.1.8.7 integer read-write
Setting this variable to 'cancel' will cause the agent to issue instructions to the UPS to cancel all outstanding commands, such as lcUpsControlOutputOff, lcUpsControlOutputOn, lcUpsControlUnixShutdown. Enumeration: 'cancel': 2, 'unknown': 1.
                             lcUpsControlRebootAgentDelay 1.3.6.1.4.1.476.1.1.1.1.8.8 integer read-write
Setting this object causes the agent to reboot after the indicated number of seconds have expired. The value will count down until the event takes place. The command can be cancelled by setting lcUpsControlCancleCommand to the value cancel.
                         lcUpsNominal 1.3.6.1.4.1.476.1.1.1.1.9
                             lcUpsNominalOutputVoltage 1.3.6.1.4.1.476.1.1.1.1.9.1 integer read-write
The nominal output voltage. (Unit of measure: volt)
                             lcUpsNominalInputVoltage 1.3.6.1.4.1.476.1.1.1.1.9.2 integer read-write
The nominal input voltage. (Unit of measure: volt)
                             lcUpsNominalOutputVA 1.3.6.1.4.1.476.1.1.1.1.9.3 integer read-write
The nominal Volt-Amp rating.
                             lcUpsNominalOutputWatts 1.3.6.1.4.1.476.1.1.1.1.9.4 integer read-write
The nominal power rating. (Unit of measure: watt)
                             lcUpsNominalOutputFreq 1.3.6.1.4.1.476.1.1.1.1.9.5 integer read-write
The nominal output frequency. (Unit of measure: Hertz)
                             lcUpsNominalInputFreq 1.3.6.1.4.1.476.1.1.1.1.9.6 integer read-write
The nominal input frequency. (Unit of measure: Hertz)
                         lcUpsTraps 1.3.6.1.4.1.476.1.1.1.1.11
                                 lcUpsOverloadWarningTrap 1.3.6.1.4.1.476.1.1.1.1.110.1
An lcUpsOverloadWarningTrap signifies that the UPS has detected an Overload condition where the output load has exceeded the UPS's rated capacity.
                                 lcUpsOnBatteryTrap 1.3.6.1.4.1.476.1.1.1.1.110.3
An lcUpsOnBatteryTrap signifies that the UPS is currently on Battery Power.
                                 lcUpsLowBatteryWarningTrap 1.3.6.1.4.1.476.1.1.1.1.110.4
An lcUpsLowBatteryWarningTrap signifies that the UPS has entered a Low Battery state.
                                 lcUpsUtilPowerFailedTrap 1.3.6.1.4.1.476.1.1.1.1.110.6
An lcUpsUtilPowerFailedTrap signifies that the utility power input to the UPS has been lost.
                                 lcUpsUtilPowerRestoredTrap 1.3.6.1.4.1.476.1.1.1.1.110.7
An lcUpsUtilPowerRestoredTrap signifies that the utility power has been restored to the UPS.
                                 lcUpsInputOverVoltageTrap 1.3.6.1.4.1.476.1.1.1.1.110.8
An lcUpsInputOverVoltageTrap signifies that the UPS has detected a high input voltage condition.
                                 lcUpsOverTempWarningTrap 1.3.6.1.4.1.476.1.1.1.1.110.9
An lcUpsOverTempWarningTrap signifies that the UPS has detected a excessive temperature condition.
                                 lcUpsAlarmTrap 1.3.6.1.4.1.476.1.1.1.1.110.11
An Alarm condition has occurred and is being reported in the lcUpsAlarmTable.
                                 lcUpsOutputOffTrap 1.3.6.1.4.1.476.1.1.1.1.110.12
An lcUpsOutputOffTrap is sent when the UPS turns all of its output off, either at the inverter or via a relay.
                                 lcUpsOutputOffWarningTrap 1.3.6.1.4.1.476.1.1.1.1.110.13
An lcUpsOutputOffWarningTrap is sent when the lcUpsControlOutputOffDelay reaches the value of lcUpsControlOutputOffTrapDelay.
                                 lcUpsOutputOnTrap 1.3.6.1.4.1.476.1.1.1.1.110.14
An lcUpsOutputOnTrap is sent when the UPS turns all of its output back on, either at the inverter or via a relay.
                                 lcUpsOutputOnWarningTrap 1.3.6.1.4.1.476.1.1.1.1.110.15
An lcUpsOutputOnWarningTrap is sent when the lcUpsControlOutputOnDelay reaches the value of lcUpsControlOutputOnTrapDelay.
                                 lcUpsUnixShutdownTrap 1.3.6.1.4.1.476.1.1.1.1.110.16
An lcUpsUnixShutodwnTrap is sent 2 seconds before the UPS is scheduled to perform a Unix Shutdown.
                                 lcUpsUnixShutdownWarningTrap 1.3.6.1.4.1.476.1.1.1.1.110.17
An lcUpsUnixShutdownWarningTrap is sent when the lcUpsControlUnixShudownDelay reaches the value of lcUpsControlUnixShutdownTrapDelay.
                     luUPStationS 1.3.6.1.4.1.476.1.1.1.2
                         lsUpsIdent 1.3.6.1.4.1.476.1.1.1.2.1
                             lsUpsIdentFirmwareVersion 1.3.6.1.4.1.476.1.1.1.2.1.1 displaystring read-only
The firmware revision level of the UPS.
                         lsUpsAlarm 1.3.6.1.4.1.476.1.1.1.2.6
                             lsUpsAlarmConditions 1.3.6.1.4.1.476.1.1.1.2.6.1
                         lsUpsTraps 1.3.6.1.4.1.476.1.1.1.2.11
                         lsUpsConfig 1.3.6.1.4.1.476.1.1.1.2.12
                               lsUpsConfigBypassInstalled 1.3.6.1.4.1.476.1.1.1.2.12.1 integer read-only
Indicates if a bypass is installed in the UPS. Enumeration: 'unknown': 1, 'yes': 2, 'no': 3.
                         lsUpsBypass 1.3.6.1.4.1.476.1.1.1.2.13
                               lsUpsOnBypass 1.3.6.1.4.1.476.1.1.1.2.13.1 integer read-only
Indicates that the UPS is currently on bypass. Enumeration: 'unknown': 1, 'yes': 2, 'no': 3.
                               lsUpsBypassFrequency 1.3.6.1.4.1.476.1.1.1.2.13.2 integer read-only
The current bypass frequency. (Unit of measure: Hertz)
                               lsUpsBypassNumLines 1.3.6.1.4.1.476.1.1.1.2.13.3 integer read-only
The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
                               lsUpsBypassTable 1.3.6.1.4.1.476.1.1.1.2.13.4 no-access
                                   lsUpsBypassEntry 1.3.6.1.4.1.476.1.1.1.2.13.4.1 no-access
                                       lsUpsBypassLine 1.3.6.1.4.1.476.1.1.1.2.13.4.1.1 integer read-only
The bypass Line.
                                       lsUpsBypassVoltage 1.3.6.1.4.1.476.1.1.1.2.13.4.1.2 integer read-only
The bypass voltage. (Unit of measure: Volt)
                                       lsUpsBypassCurrent 1.3.6.1.4.1.476.1.1.1.2.13.4.1.3 integer read-only
The bypass current. (Unit of measure: Amp)
                     luSeries300 1.3.6.1.4.1.476.1.1.1.5
                 luExperimental 1.3.6.1.4.1.476.1.1.2
                 luPrivate 1.3.6.1.4.1.476.1.1.3